SENSBLUE ATLAS: Difference between revisions
No edit summary |
|||
| Line 565: | Line 565: | ||
==== Top View ==== | ==== Top View ==== | ||
[[File:Atlas topview.png|center|frameless|688x688px]] | [[File:Atlas topview.png|center|frameless|688x688px]] | ||
=== 21. System Type === | |||
'''Raspian''' | |||
Debian GNU/Linux 13 (trixie) Version 13.2 Linux atlas 6.12.47 +rpt-rpi-v8 #1 SMP PREEMPT | |||
Debian 1 :6.12.47-1 +rpt1 (2025-09-16) aarch64 GNU/Linux. | |||
=== 22. Network Information === | |||
There is three ways to connect to the device. IP and state of the connection be checked on the LCD Network Interface. | |||
==== 22.1 Eth1 (ethO) ==== | |||
Client dynamic IP obtained by DHCP server. | |||
==== 22.2 Eth2 (eth1) ==== | |||
Static IP: '''93.48.86.253''' | |||
==== 22.3 Access Point (wlanO) ==== | |||
IP: '''192.168.30.1''' | |||
=== 23. Software Information === | |||
{| class="wikitable" | |||
| | |||
|'''Node-Red''' | |||
|'''Grafana''' | |||
|'''lnfluxDB''' | |||
|- | |||
|Version | |||
|4.1.4 | |||
|12.3.1 | |||
|2.8.0 | |||
|- | |||
|Port | |||
|1880 | |||
|3000 | |||
|8086 | |||
|- | |||
|State | |||
|Clean | |||
|Clean | |||
|Clean | |||
|- | |||
|Authentication | |||
|None | |||
|User/Pass (admin/admin) | |||
|Not defined, configured on first time interface login. | |||
|- | |||
|GUI on | |||
|http://<device-ip>:1880 | |||
|http://<device-ip>:3000 | |||
|http://<device-ip>:8086 | |||
|} | |||
=== 24. MQTT Broker === | |||
port: 1883 | |||
address: AP-> 192.168.30.1 | |||
Eth1: '''93.48.86.253''' | |||
user: < not needed> | |||
login <not needed> | |||
=== 25. Relay Outputs Actor === | |||
==== 25.1 App Interfacing ==== | |||
User App interface and functionalities exposed to the open part of the MQTT broker. Simplified interface to configure and obtain peripherals data. Connecting to the broker for this Area requires no credentials. | |||
===== 25.1.1 Set/reset digital output pin/pins state ===== | |||
Both relays '''default''' state is '''open'''. | |||
Req-Topic: relayOutputs/config/in | |||
Revision as of 16:09, 12 March 2026

Datasheet
2. Table of SENSBLUE ATLAS Reference ID Model Number
| Paxxxxxxxx | |||||
| PAxxxxxxxx |
3. General Description
SENSBLUE ATLAS is a single board computer that connects sensors and assets, runs control logic and ships to production without platform changes.
Designed for industrial teams who need one dependable path from experiments to operations.
3.1 Key Features
Processor:
- Raspberry Pi CM4 (quad-core Cortex-A72)
I/O:
- 12 DO (Digital Outputs)
- 6 AI (Analog Inputs)
- 2 relays
Industrial Bus:
- RS-485
- CAN
- 2× Ethernet port (Independently managed)
Communication:
- Integrated LTE
- Wi-Fi
- BLE
- USB
Interface & Services:
- 1.47″ IPS TFT display + joystick for local setup and feedback.
- Includes 1 GB of data (up to 500 MB LTE + 500 MB DB storage) via sensblue.cloud — no external SIM required.
- EU-hosted servers, TLS, weekly backups, VPN on request.
- Other versions under request.
4. Hardware Specifications
| Parameter | Specification |
|---|---|
| Platform | Raspberry Pi Compute Module 4 (CM4) |
| Processor | Broadcom BCM2711 Quad-core Cortex-A72 (ARM v8) |
| CPU Frequency | 1.5 GHz |
| RAM | 4GB LPDDR4 |
| Storage | 32 GB eMMC |
| Selected Variant | CM4102032-4 GB RAM/ 32 GB eMMC / Wi-Fi / BLE |
| PCle | 1 x PCle Gen 2.0 (1 lane) |
| HDMI | 1 interfaces |
| USB | 2 x USB 2.0 |
5. Power
| Parameter | Specification |
|---|---|
| Input voltage | 12-24 VDC ± 5% |
| Reverse polarity protection | Yes |
| Overcurrent protection | Resettable PTC fuse |
| Surge protection | TVS clamp for transient events |
| Isolation | No isolation |
| Typical consumption | < 15 W |
| Maximum consumption | 25 W (all peripherals active) |
6. Digital Inputs
| Parameter | Specification |
|---|---|
| Channels | 4 |
| Input voltage | 0-24 VDC |
| Logic LOW | Acording to EN 61131-2 Type I and Ill |
| Logic HIGH | Acording to EN 61131-2 Type I and Ill |
| Input type | Sourcing (PNP) |
| Input current | Acording to EN 61131-2 Type I and Ill |
| Isolation | Funcional Safety Gavanic isolation |
| Isolation Voltage | Functional isolation between channels on the field side +- 60V |
| Isolation Voltage DIN VDE V 0884-11 | Maximum working isolation voltage 400V RMS |
| Isolation Voltage DIN VDE V 0884-11 | Maximum surge isolation voltage 1 kV RMS |
| Special feature | Can be used as fast inputs until 100Hz |
7. Digital Outputs (Relay)
| Parameter | Specification |
|---|---|
| Channels | 2 |
| Type | Mechanical relay |
| Switching capacity | 2 A@ 30 VDC |
| Isolation | 1000 VAC galvanic isolation |
| Lifetime (nominal load) | ≥ 100,000 cycles |
| Lifetime (no load) | ≥ 100,000,000 cycles |
8. Digital Outputs (Transistor/ SSR)
| Parameter | Specification |
|---|---|
| Channels | 8 |
| Type | PNP (sourcing) SSR |
| Maximum current | 300 mA per channel |
| Maximum voltage | 24 VDC |
| Isolation | Funcional Safety Gavanic isolation |
| Isolation Voltage DIN VDE V 0884-17 | Maximum transient isolation voltage 1 kV RMS |
9. Analog Inputs
| Parameter | Specification |
|---|---|
| Channels | 4 |
| Mode | Voltage or current configurable per channel |
| Voltage range | 0-10 V |
| Current range | 0/4-20 mA |
| ADC resolution | 16 bits |
| ADC Sample Rate | 32 samples/sec |
| Accuracy | ≤ ±1.0% FSR |
| Input impedance (voltage) | > 100 kΩ |
| Input impedance (current) | 100 Ω |
| Protection | TVS + analog filtering |
| Sampling rate | ≥ 10 Hz per channel |
| Isolation | Funcional Safety Gavanic isolation |
| Isolation Voltage | Maximum transient isolation voltage 1 kV RMS |
10. Analog Outputs
| Parameter | Specification |
|---|---|
| Channels | 2 |
| Output type | Current |
| Range | 0-20 mA |
| Optional range | 4-20 mA (software configurable) |
| Resolution | 12 |
| Accuracy | ≤ ±1.0% FSR |
| Isolation | Funcional Safety Gavanic isolation |
| Isolation Voltage | Maximum transient isolation voltage 1 kV RMS |
11. Communication Interfaces
11.1 Ethernet
| Parameter | Specification |
|---|---|
| Ports | 2 x RJ45 |
| Port 1 | 10/100 Mbps |
| Port 2 | 0/100/1000 Mbps (native CM4) |
| Indicators | Link + Activity LEDs |
11.2 RS-485
| Parameter | Specification |
|---|---|
| Mode | Half-duplex |
| Control | TX_EN line |
| Protocol | Transparent/ any |
| Isolation | None |
11.3 USB
| Parameter | Specification |
|---|---|
| Ports | 2 |
| Type | USB-A |
| Standard | USB 2.0 Host |
| Maximum current | 400 mA per port |
| Protection | Overcurrent protection |
11.4 HDMI
| Parameter | Specification |
|---|---|
| Ports | 1 |
| Connector | HDMI full-size |
| Maximum resolution | Depends on CM4 and OS |
12. RF Communications
| Technology | Specification |
|---|---|
| Wi-Fi | Integrated in CM4 |
| BLE | Integrated in CM4 |
| LTE | M.2 NGFF modem SIM7600G |
| SIM | External access |
12.1 Antenna Connectors
| Connector | Usage |
|---|---|
| RP-SMA | Wi-Fi / BLE |
| SMA | LTE |
13. Local Peripherals
| Peripheral | Description |
|---|---|
| Temperature sensor | Internal board temperature monitoring |
| Non-volatile memory | Persistent storage |
| Security IC | Microchip ATECC608A |
| RTC | Real Time Clock with battery backup |
14. HDMI
14. 1 Display
| Parameter | Specification |
|---|---|
| Type | IPS TFT LCD |
| Interface | SPI |
| Size | 1.47" |
| Resolution | ≥ 172 X 320 |
| Backlight | LED |
| Mounting | Front mounted with transparent window |
14. 2 Joystick
| Parameter | Specification |
|---|---|
| Positions | 5 (Up/ Down/ Left/ Right/ Enter) |
| Type | Mechanical tactile switch |
| Interface | GPIO Expander |
15. Mechanical
| Parameter | Specification |
|---|---|
| Mounting | DIN rail (EN 60715) |
| Enclosure | MAT0091092 (same as iSense / iCee) |
| Protection rating | IP20 |
| Mounting method | DIN rail snap-fit |
16. Environmental
| Parameter | Specification |
|---|---|
| Operating temperature | -10 °C to +60 °C |
| Storage temperature | -20 °C to +80 °C |
| Humidity | 5-95% non-condensing |
| Vibration | IEC 60068-2-6 |
| Shock | IEC 60068-2-27 |
17. Certifications
| Certification | Standard |
|---|---|
| CE | Yes |
| EMC | 2014/30/EU |
| Radio | 2014/53/EU (RED) |
| Ro HS | 2011/65/EU |
18. Connectivity
| Parameter | Specification |
|---|---|
| Connector type | Pluggable System Terminal Block |
| Pitch | 3.5 mm |
| Layout | Dual-row |
| Identification | Side panel silk screen |
| Fixation | Mechanical locking or spring clamp |
| Protection | Mechanical reverse insertion protection |
19. Expansion
| Feature | Description |
|---|---|
| Piggyback area | Reserved PCB area |
| Compatibility | Fully compatible with existing FW |
| Power rails available | Vin, 5 V, 3.3 V |
| Interfaces available | 12C, SPI, UART, GPIO |
| External 1/0 lines | 32 lines routed to external connectors |
| Storage expansion | M.2 NVMe SSD connector |
20. Mechanical Drawings
Front View

Bottom View

Top View

21. System Type
Raspian
Debian GNU/Linux 13 (trixie) Version 13.2 Linux atlas 6.12.47 +rpt-rpi-v8 #1 SMP PREEMPT
Debian 1 :6.12.47-1 +rpt1 (2025-09-16) aarch64 GNU/Linux.
22. Network Information
There is three ways to connect to the device. IP and state of the connection be checked on the LCD Network Interface.
22.1 Eth1 (ethO)
Client dynamic IP obtained by DHCP server.
22.2 Eth2 (eth1)
Static IP: 93.48.86.253
22.3 Access Point (wlanO)
IP: 192.168.30.1
23. Software Information
| Node-Red | Grafana | lnfluxDB | |
| Version | 4.1.4 | 12.3.1 | 2.8.0 |
| Port | 1880 | 3000 | 8086 |
| State | Clean | Clean | Clean |
| Authentication | None | User/Pass (admin/admin) | Not defined, configured on first time interface login. |
| GUI on | http://<device-ip>:1880 | http://<device-ip>:3000 | http://<device-ip>:8086 |
24. MQTT Broker
port: 1883
address: AP-> 192.168.30.1
Eth1: 93.48.86.253
user: < not needed>
login <not needed>
25. Relay Outputs Actor
25.1 App Interfacing
User App interface and functionalities exposed to the open part of the MQTT broker. Simplified interface to configure and obtain peripherals data. Connecting to the broker for this Area requires no credentials.
25.1.1 Set/reset digital output pin/pins state
Both relays default state is open.
Req-Topic: relayOutputs/config/in